Shen Shuizhen,Huang Zhongke,Zhao Zhixin,et al.Application of vacuum drainage technology in the renovation of radioactive wastewater treatment system in a hospital[J].Chinese Journal of Radiological Medicine and Protection,2024,44(12):1063-1068
Application of vacuum drainage technology in the renovation of radioactive wastewater treatment system in a hospital
Received:August 05, 2024  
DOI:10.3760/cma.j.cn112271-20240805-00297
KeyWords:Vacuum drainage technology  Hospital  Radioactive waste water  Decay pool
FundProject:
Author NameAffiliationE-mail
Shen Shuizhen Sir Run Run Shaw Hospital Affiliated with Zhejiang University School of Medicine, Hangzhou 310016, China  
Huang Zhongke Sir Run Run Shaw Hospital Affiliated with Zhejiang University School of Medicine, Hangzhou 310016, China 3200021@zju.edu.cn 
Zhao Zhixin Department of Occupational Health and Radiation Hygiene, Hangzhou Hospital for the Prevention and Treatment of Occupational Disease, Hangzhou 310014, China  
Wang Haihua Department of Occupational Health and Radiation Hygiene, Hangzhou Hospital for the Prevention and Treatment of Occupational Disease, Hangzhou 310014, China  
Liao Yan Zhejiang Province Environmental Radiation Monitoring Center, State Environmental Protection Key Laboratory of Environmental Radiation Monitoring, Hangzhou 310012, China  
Hits: 1822
Download times: 699
Abstract::
      Objective To study the application value of vacuum drainage technology in radioactive wastewater discharge system of hospitals, and provide theoretical basis and reference for relevant institutes to design or renovate their radioactive wastewater discharge systems. Methods Based on the composition of vacuum drainage system and gravity drainage system, the differences in water consumption and other factors of different systems were theoretically evaluated. To take the radioactive wastewater discharge system in a hospital as a research example, the storable periods of the fixed decay pool were calculated by using the two different drainage techniques. Results Compared with the traditional gravity drainage technology, the vacuum drainage technology could save a lot of water and significantly reduce wastewater discharge. The water consumption was 16% of that of ordinary toilets with gravity drainage. By using the vacuum drainage technology to reform the radioactive wastewater discharge system of the hospital under the same amount of diagnosis and treatment workload, the storable period of radioactive wastewater could be extended by nearly three times,from 92.5 d before the renovation to 297 d after the renovation, without increasing the capacity of the decay pool. After the transformation, the total activity and volumetric activity concentration of 131I when discharging wastewater from each decay tank could be reduced to 4 096 Bq and 0.17 Bq/L, respectively, and the volumetric activity concentration was much lower than the national emission requirements. Conclusions Vacuum drainage can significantly reduce wastewater production, and is worth promoting and applying in nuclear medicine departments.
HTML  View Full Text  View/Add Comment  Download reader
Close

Copyright©    Editorial Office of Chinese Journal of Radiological Medicine and Protection    

Beijing ICP No. 05020547 -2

Address: 2 Xinkang Street, Dewai, Beijing 100088, China

Telephone:010-62389620; Email:cjrmp@cjrmp.sina.net

Technical Support:Beijing E-tiller CO.,LTD.

Visitors:12030763  On-line:0

v
Scan QR Code
&et=DCA5CABA83612A9445EB2738379621EB17D74FFBAD096F253401B4E652F5CA24279A9D65F274267FF22464A9FE18A51E0254BF3220C06F702F92478B090E9C98A4B322F313A02593E0CFA449BED50B720299C9B22CC5EB1B46706B7F4ED4163B3B3C2147B81F747D4C2047F582A54E2FE403BA7B9A97BE0D&pcid=A9DB1C13C87CE289EA38239A9433C9DC&cid=D4D466D60FDC1A5A&jid=5E4353813E091AB841B02B880782B82C&yid=B80136CCD8DCBAA1&aid=03C7CF8E4B73A4ED0088F58A4771FAD0&vid=&iid=59906B3B2830C2C5&sid=EE05CC1F800E4629&eid=305A58D956DD6BAF&fileno=20241211&flag=1&is_more=0"> var my_pcid="A9DB1C13C87CE289EA38239A9433C9DC"; var my_cid="D4D466D60FDC1A5A"; var my_jid="5E4353813E091AB841B02B880782B82C"; var my_yid="B80136CCD8DCBAA1"; var my_aid="03C7CF8E4B73A4ED0088F58A4771FAD0";